<?xml version="1.0" encoding="UTF-8"?><?xml-stylesheet type="text/xsl" href="static/style.xsl"?><OAI-PMH xmlns="http://www.openarchives.org/OAI/2.0/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/ http://www.openarchives.org/OAI/2.0/OAI-PMH.xsd"><responseDate>2026-11-03T04:51:44Z</responseDate><request verb="GetRecord" identifier="oai:riubu.ubu.es:10259/7540" metadataPrefix="edm">https://riubu.ubu.es/oai/request</request><GetRecord><record><header><identifier>oai:riubu.ubu.es:10259/7540</identifier><datestamp>2024-05-14T09:45:32Z</datestamp><setSpec>com_10259_6155</setSpec><setSpec>com_10259_4266</setSpec><setSpec>com_10259.4_106</setSpec><setSpec>com_10259_2604</setSpec><setSpec>col_10259_6156</setSpec></header><metadata><rdf:RDF xmlns:rdf="http://www.w3.org/1999/02/22-rdf-syntax-ns#" xmlns:doc="http://www.lyncode.com/xoai" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xmlns:ore="http://www.openarchives.org/ore/terms/" xmlns:dcterms="http://purl.org/dc/terms/" xmlns:ds="http://dspace.org/ds/elements/1.1/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:edm="http://www.europeana.eu/schemas/edm/" xsi:schemaLocation="http://www.w3.org/1999/02/22-rdf-syntax-ns# http://www.europeana.eu/schemas/edm/EDM.xsd">
<edm:ProvidedCHO rdf:about="http://hdl.handle.net/10259/7540">
<dc:creator>Martínez, Raquel</dc:creator>
<dc:creator>Arroyo, Alberto</dc:creator>
<dc:creator>Pigazo, Alberto</dc:creator>
<dc:creator>Manana, Mario</dc:creator>
<dc:creator>Bayona Blanco, Eduardo</dc:creator>
<dc:creator>Azcondo, Francisco J.</dc:creator>
<dc:creator>Bustamante, Sergio</dc:creator>
<dc:creator>Laso, Alberto</dc:creator>
<dc:date>2022-12</dc:date>
<dc:description>Power-quality events and operation transients in power systems (PS) with isolated neutral&#xd;
can saturate inductive voltage transformers (IVT), which, when interacting with the overhead and&#xd;
underground cable capacitances, can cause ferroresonance events in the local PS. This abnormal&#xd;
operating mode can partially or totally damage the transformers and switchgears within the affected&#xd;
PS. Distribution system operators (DSO) can minimize these effects by detecting ferroresonance events&#xd;
accurately and fast enough and changing the mode of operation accordingly. Direct detection methods,&#xd;
i.e., based on voltage measurements, are reliable, but the massive deployment of this solution is&#xd;
relatively expensive; i.e., power quality analyzers cost thousands of USD. Alternatively, indirect&#xd;
detection methods are also available, e.g., IVT vibration measurements with accelerometers costing&#xd;
hundreds of USD, but their reliability depends on the installation method used. This manuscript&#xd;
proposes using the acoustic noise caused by magnetostriction forces within the IVT core during&#xd;
ferroresonance events to detect their occurrence. Compared to other indirect methods, electret&#xd;
condenser microphones with preamplifying stage cost less than USD 10 and are less sensitive to&#xd;
the installation procedure. The proposed method is validated experimentally, and its performance&#xd;
compared to IVT vibration measurements one by using the same detection methodology.</dc:description>
<dc:format>application/pdf</dc:format>
<dc:identifier>http://hdl.handle.net/10259/7540</dc:identifier>
<dc:language>eng</dc:language>
<dc:publisher>MDPI</dc:publisher>
<dc:title>Acoustic Noise-Based Detection of Ferroresonance Events in Isolated Neutral Power Systems with Inductive Voltage Transformers</dc:title>
<dc:type>info:eu-repo/semantics/article</dc:type>
<edm:type>TEXT</edm:type>
</edm:ProvidedCHO>
<ore:Aggregation rdf:about="http://hdl.handle.net/10259/7540#aggregation">
<edm:aggregatedCHO rdf:resource="http://hdl.handle.net/10259/7540"/>
<edm:dataProvider>RIUBU. Repositorio Institucional de la Universidad de Burgos</edm:dataProvider>
<edm:isShownAt rdf:resource="http://hdl.handle.net/10259/7540"/>
<edm:isShownBy rdf:resource="https://riubu.ubu.es/bitstream/10259/7540/1/Martinez-sensors_2022.pdf"/>
<edm:object rdf:resource="https://riubu.ubu.es/bitstream/10259/7540/4/Martinez-sensors_2022.pdf.jpg"/>
<edm:provider>Hispana</edm:provider>
<edm:rights rdf:resource="http://creativecommons.org/licenses/by/4.0/"/>
</ore:Aggregation>
<edm:WebResource rdf:about="https://riubu.ubu.es/bitstream/10259/7540/1/Martinez-sensors_2022.pdf">
<edm:rights rdf:resource="http://creativecommons.org/licenses/by/4.0/"/>
</edm:WebResource>
</rdf:RDF></metadata></record></GetRecord></OAI-PMH>