dc.contributor.authorDiez Mediavilla, Montserrat 
dc.contributor.authorDieste Velasco, Mª Isabel 
dc.contributor.authorRodríguez Amigo, María del Carmen 
dc.contributor.authorGarcía Calderón, Teófilo 
dc.contributor.authorAlonso Tristán, Cristina 
dc.date.accessioned2018-01-11T08:30:58Z
dc.date.available2018-01-11T08:30:58Z
dc.date.issued2013-12
dc.identifier.issn0196-8904
dc.identifier.urihttp://hdl.handle.net/10259/4695
dc.description.abstractA new procedure is presented to analyse the performance of grid-tied PV facilities. It needs limited amounts of data that are easily sourced and is based on knowledge of the analysed system and its mode of operation. The procedure is applied, in a case study, to compare real PV production at two 100 kWp grid-connected PV installations. Located in the same geographical region, the installation of these two facilities followed the same construction criteria – PV panels, panel support system and wiring – and the facilities were exposed to the same atmospheric temperature and solar radiation. They differ with regard to their inverter technology: one facility uses an inverter with an integrated transformer system and the other uses a transformerless inverter. The results show that the transformerless inverter system performed better than the isolated system by a factor of 1.2%, which, in economic terms, represents more than 2000 €/yearen
dc.description.sponsorshipSpanish Government (Grant ENE2011-27511) and the Department of Culture and Education of the Regional Government of Castilla y León, Spain (Grant BU358A12-2).en
dc.format.mimetypeapplication/pdf
dc.language.isoenges
dc.publisherElsevieren
dc.relation.ispartofEnergy Conversion and Management. 2013, V. 76, p. 893-898en
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 International
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/
dc.subjectPV facilitiesen
dc.subjectPerformanceen
dc.subjectTransformerless inverteren
dc.subjectIsolated inverteren
dc.subject.otherElectric engineeringen
dc.subject.otherIngeniería eléctricaes
dc.titlePerformance of grid-tied PV facilities: a case study based on real dataen
dc.typeinfo:eu-repo/semantics/article
dc.rights.accessRightsinfo:eu-repo/semantics/openAccess
dc.relation.publisherversionhttps://doi.org/10.1016/j.enconman.2013.08.035
dc.identifier.doi10.1016/j.enconman.2013.08.035
dc.relation.projectIDinfo:eu-repo/grantAgreement/MINECO/ENE2011-27511
dc.relation.projectIDinfo:eu-repo/grantAgreement/JCyL/BU358A12-2
dc.type.hasVersioninfo:eu-repo/semantics/acceptedVersionen